2/0-2/0-1 Converse Triplex URD Cable Application
Single URD cable is rated at 600V for underground secondary distribution not exceeding 90˚C. It may be directly buried in earth or installed in duct in both wet or dry locations.
2/0-2/0-1 Converse Triplex URD Cable Construction
1. Conductor: Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum
2. Insulation: Cross Linked Polyethylene (XLPE)
3.Neutral conductor in black thermoset cross-linked polyethylene (XLPE) identified by yellow striping or full yellow jacket.
2/0-2/0-1 Converse Triplex URD Cable Specifications
Code Word | Phase Conductors | Neutral Conductor | Single Phase Conduc- tor (in) |
Outside Diameter (in) |
Weight per 1000ft (lbs) |
Ampacity | |||||
Size AWG |
Strand | Insulation Thickness (MLS) |
Size AWG |
Strand | Insulation Thick- ness (MLS) |
Direct Burial |
In Duct |
||||
Erksine | 6 | 7/w | 60 | 6 | 7/w | 60 | .299 | .646 | 143 | 95 | 70 |
Vassar | 4 | 7/w | 60 | 4 | 7/w | 60 | .345 | .754 | 203 | 125 | 90 |
Stephens | 2 | M/L | 60 | 4 | M/L | 60 | .403 | .842 | 264 | 165 | 120 |
Ramapo | 2 | 7/w | 60 | 2 | 7/w | 60 | .403 | .874 | 294 | 165 | 120 |
Brenau | 1/0 | 19/w | 80 | 2 | 7/w | 60 | .522 | 1.064 | 408 | 215 | 160 |
Bergen | 1/0 | 19/w | 80 | 1/0 | 19/w | 80 | .522 | 1.133 | 465 | 215 | 160 |
Converse | 2/0 | 19/w | 80 | 1 | 19/w | 80 | .566 | 1.174 | 502 | 245 | 180 |
Hunter | 2/0 | 19/w | 80 | 2/0 | 19/w | 80 | .566 | 1.228 | 560 | 245 | 180 |
Hollins | 3/0 | 19/w | 80 | 1/0 | 19/w | 80 | .616 | 1.276 | 606 | 280 | 205 |
Sweetbriar | 4/0 | 19/w | 80 | 2/0 | 19/w | 80 | .672 | 1.389 | 739 | 315 | 240 |
Monmouth | 4/0 | 19/w | 80 | 4/0 | 19/w | 80 | .672 | 1.457 | 828 | 315 | 240 |
Pratt | 250 | 37/w | 95 | 3/0 | 19/w | 80 | .748 | 1.538 | 893 | 345 | 265 |
Wesleyan | 350 | 37/w | 95 | 4/0 | 19/w | 80 | .851 | 1.736 | 1166 | 415 | 320 |
Rider | 500 | 37/w | 95 | 350 | 37/w | 95 | .979 | 2.035 | 1663 | 495 | 395 |